Omron WS02-9094G - V1.0 Operation Manual page 143

Table of Contents

Advertisement

Number
Message
07
[IO area] must be empty. Move all
modules into other area
Note [IO area] = output area1/
output area2/ input area1/
input area2
08
Slave_User_data part of the
PROFIBUS slave parameter set
will be ignored. See slave [no]-
[name]
Note [no] = slave address
[name] = slave DTM name
09
Auto addressing will reallocate
slave I/O mapping. Would you like
to proceed?
10
Settings cannot be uploaded, unit
must be restarted. Would you like
to continue?
11
Upload is not supported.
12
After locking address it cannot be
changed any more. Would you
like to proceed?
13
DPV1 alarms are not supported
by the Master Unit and will be dis-
abled.
14
Publisher functionality is not sup-
ported by the Master Unit and will
be disabled.
15
Isochronous mode is not sup-
ported by the Master Unit and will
be disabled.
A-2
Error Messages - Configuration
The table below lists the Error messages which can be displayed by the PROFIBUS Master Unit DTM in case
there are configuration errors. Usually, these are detected either when entering, or up on download. The table
suggests corrections to the problems in the right most column.
Number
Message
00
Total I/O area size exceeds maxi-
mum
01
PROFIBUS I/O Data area overlap-
ping
128
Description
"Not used" item in the start address combo box in
output/input allocation tabs can only be selected
if there are no I/O module mapped in that area.
• OK
Close message box. Move modules
to other I/O area first.
Slave_User_data part of the slave parameter set
will not be used. The additional user parameters
in the slave parameter set are not supported by
the PROFIBUS Master Unit.
• OK
Close message box
When selecting the Auto-Addressing check box
in the Master Setup tab, all slave I/O data map-
pings will be compressed in each of the I/O map-
pings. The slave I/O mapping will be changed.
• Yes
Update slave I/O module mapping and
check checkbox.
• No
Do not update slave I/O module map
ping and uncheck checkbox.
The settings uploaded were not used by stack
• Yes: Restart the unit and upload the settings.
• No: Do nothing.
Upload is not supported
• OK: Close message box.
When sending Set Device Station Address com-
mand with 'Lock' check box is checked, the
address will be stored permanently in the Slave
device and can not be changed anymore.
• Yes: Lock option is checked.
• No: Lock option is unchecked.
Alarm settings set by the Slave DTM are not sup-
ported and will be reset.
• OK: Close message box.
Publisher functionality set by the Slave DTM is
not supported and will be reset.
• OK: Close message box.
Isochronous mode set by the Slave DTM is not
supported and will be reset.
• OK: Close message box.
Description
The I/O configuration exceeds the
maximum limit of 7168 (or 7k)
words).
Input/Output areas are overlapping
within the current configuration.
Appendix
When occurring
When selecting the "Not
Used" item from the
memory area box.
When adding a slave
DTM to the network,
which defines additional
user parameters.
When checking the
Auto-Addressing check-
box on the Master Setup
tab.
When attempting to
upload settings.
When attempting to
upload settings.
When 'Lock' check box
in the Set Device Station
Address GUI is checked.
Downloading settings
and one of the alarm bits
are set in Slave Parame-
ter Set.
Downloading settings
and bit is set in Slave
Parameter Set.
Downloading settings
and bit is set in Slave
Parameter Set.
Correction
Change configuration to reduce the
amount of I/O data to 7168 words
maximum or less.
Check the Input/Output areas and
make sure they are not overlapping.
Retry download.