Section 7 System Settings
NS-Designer Operation Manual
No.
Setting
1
Number of Opera-
tion Log Records
2
Use Ring Buffer
3
Character Code for
Log File
4
Logfile Output
Format
5
Save the data with
offset time display
format
7-1-5

Comm-All

This tab page is used to set the communications destination. Click the Comm-All Tab.
Set the number of logging records to be saved in a single file. The number of re-
cords can be set to between 0 and 1,024.
Set to 0 if it is not necessary to save records.
Select to record data in a ring buffer. When this setting is selected, if the maximum
number of items is exceeded, the oldest data is deleted and the new data is re-
corded. When this setting is not selected, no more data will be recorded once the
set maximum is reached.
Select the character code (ASCII or Unicode) for alarm/event histories, data logs,
operation logs, and error logs.
Set the format for outputting the data log to a CSV file.
Select to display the time as an offset when outputting log data from the data log
to a CSV file.