Convenient Functions

Scaling Teach
The parameter (inp) for the K3MA-F's initial setting level can be set using actual input values with the teaching function. After displaying the pa-
rameter, the actual input settings can be made with the following operation.
"T" lights to
indicate that the
parameter is valid
for teaching.
OUT Types (Comparative Output Models Only)
OUT 1 and OUT 2 can be set to operate in one of the three following modes in accordance with the compared values:
• Upper limit (High Acting):
The output is turned ON when the measurement value is greater than its set value.
• Lower limit (Low Acting):
The output is turned ON when the measurement value is less than its set value.
• Upper and lower limits (Outside Band Acting):
An upper limit (H set value) and lower limit (L set value) can be set independently.
The output is turned ON when the measurement value is greater than upper-limit set value or less than the lower-limit set value.
Upper Limit (High Acting)
OUT1 value
Hysteresis
Measurement value
ON
Output
OFF
The three types of output operations shown above can be combined as desired. The following are examples of possible combinations.
Upper Limit 2-stage Output
OUT2
value
Measurement
value
OUT1
value
OUT2 ON
OFF
ON
OUT1
OFF
Parameter Initialization
This function returns all of the parameters to their initial values.
Parameter
Setting value
init
off
on
Use this to reset the K3MA-F after returning it to its factory-set condi-
tion.
Monitor mode
Next parameter
Lower Limit (Low Acting)
Measurement value
OUT1 value
ON
Output
OFF
Threshold Output
OUT2 upper-limit
value
OUT1 upper-limit
value
OUT1 lower-limit
value
OUT2 lower-limit
value
OUT2 ON
OFF
ON
OUT1
OFF
Meaning
---
Initializes all parame-
ters.
Teaching mode
"T" flashes.
Use
to
register and shift to
monitor mode.
Normal change
"T" turns OFF.
Measurement value
Hysteresis
Combination of Upper Limit and
Upper/Lower Limits
OUT2 upper-limit
value
Measurement
value
OUT1 value
OUT2 lower-limit
value
Frequency/Rate Meter
Use
to shift to
the next parameter
without registering.
Upper and Lower Limits
(Outside Band Acting)
OUT1 upper-limit
Hysteresis
value
OUT1 lower-limit
value
ON
Output
OFF
Measurement
value
OUT2 ON
OFF
ON
OUT1
OFF
K3MA-F
Hysteresis
7