The TEST and START pushbuttons must be positioned in such a
way that the operator can see the protected area when he carries
out restart, test or override operations.
The F39-A11 muting lamp must be positioned in a place where it
can be seen from any operative point.
If the muting sensors are installed very near the protection
photocells, it is necessary to install the sensor receivers on the
photocell sender side to avoid interference.
The system is anyway protected from possible failures due to the
cable damage; it is necessary to prepare the wiring of all
connections so as to avoid damage to the connection cables.
The control unit must be located in a cabinet with protection
degree of at least IP54.
Muting sensor connection:
24 V
DC
Muting enable to S3 and S4
from robot system control
Muting enable to S1 and S2
from robot system control
User's manual
11 MUTE C
10 MUTE D
9 MUTE A
8 MUTE B
F3SP-U5P-TGR
terminals