The TEST and START pushbuttons must be positioned in such a
way that the operator can see the protected area when he carries
out restart, test or override operations.
•
The F39-A11 muting lamp must be positioned in a place where it
can be seen from any operative point.
•
If the muting sensors are installed very near the protection
photocells, it is necessary to install the sensor receivers on the
photocell sender side to avoid interference.
•
The system is anyway protected from possible failures due to the
cable damage; it is necessary to prepare the wiring of all
connections so as to avoid damage to the connection cables.
•
The control unit must be located in a cabinet with protection
degree of at least IP54.
Muting sensor connection:
24 V
DC
Muting enable to S3 and S4
from robot system control
Muting enable to S1 and S2
from robot system control
User's manual
11 MUTE C
10 MUTE D
9 MUTE A
8 MUTE B
F3SP-U5P-TGR
terminals
22