Ladder Programming Examples

4-6
Ladder Programming Examples
4-6-1

RUN/STOP Programming Examples

Operation
78
7. Click the OK Button, and return to the master's Edit Device Parameters
Window.
8. Select the General Tab, and click the Download Button to write the set I/O
memory allocations to the master.
Note Always click the OK Button to exit the master's Edit Device Parameters Win-
dow. If the Cancel Button or the
invalid.
The ladder programming example here is for the following execution condi-
tions.
• Using simple I/O allocation to allocate data in the fixed allocation area 1 of
a CS/CJ-series DeviceNet Unit (OUT Area = CIO 3200 to CIO 3263, IN
Area = CIO 3300 to CIO 3363).
• Executes RUN or STOP for the TC2 (Unit 0, ch1).
• The bit in the first word + 2 words of the OUT Area is allocated by default
to the RUN/STOP Bit (CIO 320200).
• RUN is executed when the RUN/STOP Bit (CIO 320200) turns ON for the
execution condition 000000, after which the OUT Enable Bit turns ON.
When the RUN/STOP Confirmation Flag (CIO 330200) turns ON, the
OUT Enable Bit turns OFF.
• STOP is executed when the RUN/STOP Bit (CIO 320200) turns OFF for
the execution condition 000100, after which the OUT Enable Bit turns ON.
Then, when the RUN/STOP Confirmation Flag (CIO 330200) turns OFF,
the OUT Enable Bit turns OFF.
Section 4-6
Button is clicked, the settings will be