Part Names And Functions; Part Names - Omron EJ1 - 07-2008 Operation Manual

Devicenet communications unit for ej1 temperature controllers
Table of Contents

Advertisement

Part Names and Functions

3-1
Part Names and Functions
3-1-1

Part Names

External Dimensions
22
Node Address
Set the node address for the
DeviceNet slave.
Highest Communications Unit Number
When using simple I/O allocation, set the highest
communication unit number that is used by the
connected Temperature Controllers.
Setting DIP Switches
DIP Switches
Descriptions
Executes UpLoad/DownLoad
6 (COPY)
---
OFF
ON (For 1 to 5 sec)
5
---
Not in use
OFF OMRON Configurator is used.
4 (EDS)
ON Other manufacturer's configurator is used.
OFF UpLoad (from Temperature Controller to EJ1-DRT)
3 (UP/DN)
ON DownLoad (from EJ1-DRT to Temperature Controller)
OFF Simple assignment of I/O for TC2
2 (TC2/4)
ON Simple assignment of I/O for TC4
OFF Simple assignment of I/O given by Configurator
1 (MODE)
ON Simple assignment of I/O
DeviceNet Communications Connector
This connector connects the DeviceNet network
communications cable.
The DeviceNet communications power is also supplied
through this connector.
The required FCK2.5/5-STF-5.08AU connector
(Phoenix Contact) is provided with the Unit.
20
Front Panel
OFF
82.2
65
Section 3-1
EJ1N
10
DRT
NODE
ADR
MS
1
Indicators
NS
MAX
TS
No.
COPY
EDS
UP/DN
TC2/4
MODE
NO
(Unit: mm)