Omron E5ZN Manual page 5

Modular temperature controller e5zn series
Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

■ Communications
(Host Communications)
Transmission line
RS-485 multipoint
connection method
Communications
RS-485 (2-wire, half-duplex)
method
Synchronization
Start-stop synchronization
method
Baud rate
4,800, 9,600, 19,200, or 38,400 bps
Transmission code
ASCII
Data bit length
7 or 8 bits
(See note.)
Stop bit length (See
1 or 2 bits
note.)
Vertical parity (none, even, odd)
Error detection
BCC (block check character)
Flow control
None
Interface
RS-485
Retry function
None
Number of Units that
can be connected in
16 Units max. (32 channels)
parallel
Note: The baud rate, data bit length, stop bit length, and vertical par-
ity can all be set independently as host communications set-
tings.
■ Setting Display Unit (Order
Separately)
Ratings and Characteristics
Power supply voltage
24 VDC
Allowable voltage
85% to 110% of the rated power supply
range
voltage
Power consumption
Approx. 1 W
7-segment digital display and single-color
Display method
display
10 to 55×C (with no icing or condensa-
Ambient operating
tion)
temperature
For 3 years of assured use: 10 to 50×C
Ambient operating hu-
25% to 85%
midity
25 to 65×C (with no icing or condensa-
Storage temperature
tion)
Communications
RS-485 (half-duplex)
method
Communications for-
Fixed
mat
Insulation resistance
20 MW min. (at 500 VDC)
1,500 VAC for 1 minute at 50 or 60 Hz (be-
Dielectric strength
tween unlike terminals of charged parts)
10 to 55 Hz, 20 m/s
Vibration resistance
and Z directions
300 m/s
Shock resistance
±Z directions
Front panel: IP50
Enclosure ratings
Rear case: IP20
Terminal case: IP00
EEPROM (non-volatile memory) (Number
Memory protection
of writes: 100,000)
Approx. 100 g
Weight
Mounting bracket: Approx. 10 g
2
for 2 hrs each in X, Y,
2
max., 3 times each in ±X, ±Y, and
■ Current Transformer (CT)
Ratings (Order Separately)
Dielectric strength
1,000 VAC (1 minute)
Vibration resistance
50 Hz, 98 m/s
E54-CT1: Approx. 11.5 g
Weight
E54-CT3: Approx. 50 g
Accessories
Armature (2)
(E54-CT3 only)
Plug (2)
■ Heater Burnout Alarm
Characteristics
Maximum heater
Single-phase, 50 A AC (See note 1.)
current
Input current
±5% FS ±1 digit max.
readout accuracy
Heater burnout
0.0 to 50.0 A (in units of 0.1 A)
alarm setting range
(See note 2.)
Minimum detection ON
190 ms (See note 3.)
time
Note: 1. Use the K2CU-F@@A-@GS (with GATE input terminal) for
burnout detection of 3-phase heaters.
2. If the heater burnout alarm setting is set to 0.0 A, the alarm
is always OFF, and if it is set to 50.0 A the alarm is always
ON.
3. If the ON time for control output is less than 190 ms, heater
burnout detection and heater current measurement will not
be performed.
Modular Temperature Controller
2
E5ZN
I-133