External Connections - Omron E5CN Datasheet

Basic-type digital temperature controller (48 x 48 mm)
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

External Connections

A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.)
Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
E5CN
Controllers
Control output 1
Long-life relay output
250 VAC, 3 A (resistive load)
Relay output
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
mA
Current output
0 to 20 mA DC
4 to 20 mA DC
DO NOT
Load: 600
max.
USE
Option Units
Control output 2
Voltage output (for driving SSR)
12 VDC, 21 mA
E53-CNHH03N2
E53-CNHBN2
Communications
Event inputs
(RS-485) and CT2
and CT
B(+)
1 1
RS-485
1 2
A( )
E V 1
1 3
E V 2
CT2
1 4
CT1
CT1
1 5
E53-CNH03N2
E53-CN03N2
Communications
Communications
(RS-485) and CT
(RS-485)
B(+)
B(+)
1 1
RS-485
RS-485
1 2
A( )
A( )
DO NOT
1 3
DO NOT
USE
USE
1 4
DO NOT
USE
CT1
1 5
DO NOT
USE
E5CN-U
Control output 1
Relay output
(three terminals used)
SPDT, 250 VAC, 3 A
(resistive load)
Voltage output
m A
(for driving SSR)
12 VDC, 21 mA
Current output
DO NOT
4 to 20 mA DC
USE
0 to 20 mA DC
Load: 600 W max.
mA
Analog input
Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.
Control output 1
A
DO NOT
DO NOT
USE
USE
B
V
B
mA
Volt
T/c
Pt
Analog input
Temperature
input
E53-CNQ03N2
Communications
(RS-485) and
Control Output 2
1 1
B(+)
1 1
RS-485
1 2
1 2
A( )
1 3
DO NOT
1 3
USE
1 4
External
+
1 4
power supply
1 5
Control output 2
1 5
E53-CNBN2
Event inputs
1 1
1 1
1 2
1 2
E V 1
1 3
1 3
E V 2
DO NOT
1 4
1 4
USE
DO NOT
1 5
1 5
USE
Control output 1
A
DO NOT
DO NOT
USE
USE
B
V
B
Volt
T/c
Pt
Temperature
input
Basic-type Digital Temperature Controller
Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
Auxiliary output 2
Auxiliary output 1
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
E53-CNPBN2
E53-CNPHN2
Event Inputs and
External Power
External Power Supply
Supply and CT
1 1
+
External
1 1
power supply
1 2
E V 1
1 2
1 3
DO NOT
E V 2
1 3
USE
+
1 4
12 VDC,
1 4
20 mA
CT1
1 5
1 5
E53-CNQHN2
E53-CNQHHN2
Control Output 2
Control Output 2
and CT
and CT2
+
+
1 1
Control output 2
Control output 2
1 2
DO NOT
1 3
USE
CT2
1 4
CT1
CT1
1 5
Auxiliary output
250 VAC, 3 A (resistive load)
(Relay outputs)
Auxiliary output 1
Auxiliary output 2
(Control output (cooling side))
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
E53-CNP03N2
Communications (RS-485)
and External Power Supply
B(+)
1 1
12 VDC,
RS-485
20 mA
1 2
A( )
DO NOT
1 3
USE
+
1 4
External
12 VDC,
power supply
20 mA
1 5
E53-CNQBN2
Event Inputs and
Control Output 2
1 1
1 1
1 2
1 2
E V 1
1 3
1 3
E V 2
+
1 4
1 4
Control output 2
1 5
1 5
An input error is sent to the
output to which the alarm 1
function is assigned.
E5CN/E5CN-U
11