Omron E5CN Datasheet page 2

Basic-type digital temperature controller (48 x 48 mm)
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Lineup
E5CN
Basic Type
Note: All models can be used for Heating, Cooling and Heating & Cooling control
Model Number Structure
Model Number Legend
Controllers
E5CN-@ 2 M@@-@-500
1 2 3 4 5
6
1. Control Output 1
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
Y: Long-life relay output (hybrid) ✽1
2. Auxiliary Outputs ✽2
2: Two outputs
3. Option
M: Option Unit can be mounted.
4. Input Type
T: Universal thermocouple/platinum resistance thermometer
L: Analog current/voltage input
5. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
6. Case Color
Blank: Black
W: Silver (contact your local sales for more information)
7. Terminal Cover
-500: With terminal cover
Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-CN@@N2).
✽1. Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is connected because a triac is used for
switching the circuit. For details, check the conditions in Ratings.
✽2. Auxiliary outputs are contact outputs that can be used to output alarms, control or results of logic operations.
2
Basic-type Digital Temperature Controller
Terminal block
Plug-in
7
Temperature input
Analog input
Temperature input
Analog input
Option Units
E53-CN@@N2
1
2 3
4
1. Applicable Controller
CN: E5CN
2. Function 1
Blank: None
Q: Control output 2 (voltage for driving SSR)
P: Power supply for sensor
3. Function 2
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(For 3-phase heater applications, 2x CT)
B: Two event inputs
03: RS-485 communications
H03: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + RS-485 communications
HB: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + Two event inputs
HH03: Heater burnout/SSR failure/Heater overcurrent detection
(For 3-phase heater applications, 2x CT)
4. Version
N2: Applicable only to models produced after January 2008
(Box marked with N6)
E5CN/E5CN-U
2 auxiliary outputs
1 control output
2 control outputs
2 auxiliary outputs
2 auxiliary outputs
1 control output
2 control outputs
2 auxiliary outputs
2 auxiliary outputs
1 control output
2 auxiliary outputs
1 control output

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents