Specifications of Basic I/O Units
Circuit Configuration
Terminal Connections
CJ1W-OD201 Transistor Output Unit (Terminal Block, 8 Points, Sinking)
568
Output indicator
N C
A0
0
L
B0
N C
A1
1
L
B1
N C
A2
2
L
B2
N C
A3
3
L
B3
N C
4
A4
L
B4
N C
A5
5
L
B5
N C
A6
6
L
B6
N C
A7
7
B7
L
N C
A8
C O M
B8
Rated Voltage
Operating Load Voltage Range 10.2 to 26.4 V DC
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption
Fuse
External Power Supply
Weight
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used
for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O
tables.
O U T0
to
O U T7
C O M
Fuse
250 V AC max.
12 to 24 V DC
2.0 A/point, 8.0 A/Unit
10 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
20 MΩ between the external terminals and the GR
terminal (100 V DC)
1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
8 (4 points/common, 2 circuits)
5 V DC: 90 mA max.
6.3 A (1/common, 2 used)
The fuse cannot be replaced by the user.
12 to 24 V DC, 10 mA min.
110 g max.