Unit Components and Specifications
2-1-3 I/O Specifications
2-1-3-1
Input Specifications
Item
Input voltage
Input impedance
Input current
ON voltage/current
OFF voltage/current
ON delay
OFF delay
Circuit configuration
Note
Inputs
All
IN00000 to IN00001
IN00002 to IN00004
IN00005
IN00000 to IN00001
IN00002 to IN00004
IN00005
IN00000 to IN00001
IN00002 to IN00005
All
All
All
IN00000 to IN00001
IN00002 to IN00004
IN00005
The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the
PLC Setup.
+10%
24 VDC
/
–15%
2.7 kΩ
3.9 kΩ
4.7 kΩ
8 mA typical
6 mA typical
5 mA typical
17 VDC min., 5 mA
14.4 VDC min., 3.5 mA
5.0 VDC max., 1.1 mA
1 to 80 ms max. Default: 10 ms (See note.)
1 to 80 ms max. Default: 10 ms (See note.)
Specification
SECTION 2
21