5-4-4 Transfer Timing Chart in case of Errors

210.00 (R) or 210.01 (W)
(Transfer Command Bit)
206.03
(Transfer Busy Flag)
206.01
(Transfer Completion Flag)
206.02
(Transfer Error Flag)
DM(K)
(Transfer Response)
Operation
Timing
The diagram below shows the timing of the Transfer command which re-
sulted in an error. The timing is the same for reading and writing.
1.
1.
When the Transfer Command Bit is turned ON, the Transfer Busy Flag will
turn ON one PLC cycle later, and the command specified in the DM Area (L)
will be processed.
2.
When the Transfer Error Flag is turned ON, the error code is present in the
DM Area (K).
3.
When the Transfer Command Bit is turned OFF, the Transfer Busy Flag and
Transfer Error Flag will turn OFF one PLC cycle later.
Note In case of an error the Transfer Completion flag is not turned ON.
Note For the error codes see section 5-4-7.
The timing is the same as in the case of normal completion.