Type
Digital Input
(DI)
3.3.1
DI Wiring
The diagram below shows how to wire the digital input.
Figure 3-4.
1
3.4
Digital Outputs
The FB2100 flow computer with I/O option 1 includes a single digital output. The FB2100
flow computer with I/O option 2 includes two channels you can configure as digital
outputs (DO), digital inputs (DI) or pulse inputs (PI).
70
3-3. Digital input Characteristics
Number Supported
0 to 2 as follows under I/O
option 2 only:
1 or 2 non-isolated channels
on CPU board (DI/DO/PI1 and
DI/DO/PI2). Two always
present; you can configure
one, both, or neither as DIs.
Digital Input (DI) Wiring [DI/DO/PI1 & DI/DO/PI2] – (I/O Option 2)
Dry contact
Characteristics
Circuit protection
30ms input filtering
Maximum input frequency of
10 Hz
Selectable current source of 66
µA or 2 mA
Either externally driven or
internally driven and pulled to
ground by dry contact
closures or open collector
devices
When a channel is configured
as a DI it cannot be used as a
DO or PI channel