2.2.

Environmental Specifications

This section summarizes the environmental specifications for the device. For full details,
refer to the product data sheet
Table
Specification
Ambient
Temperature
Humidity
Vibration
2.3.

Required Tools

Certain tools and equipment are required for installing and servicing the flow computer.
Table
Tool
Torque wrench
2.5 mm hexagonal wrench
#1 Phillips-head
screwdriver
#2 Phillips-head
screwdriver
#3 Phillips-head
screwdriver
1/8 inch flat-head
screwdriver
7/32 inch flat-head
screwdriver
Utility knife
Wire cutters
14
2-1. Environmental Specifications
Configuration
No battery, C1D2
No Battery, C1D2,
Relay installed
Lead Acid Battery,
C1D2
ATEX/IEC Ex ec
No Battery
2-2. Required Tools
FB2100 Flow Computer
4 1 T
Aluminum
Enclosure
40°C to +80 °C
(-40 °F to +176 °F)
-40 °C to 60 °C
(-40 °F to 140 °F)
-40 °C to 45 °C
(-40 °F to 113 °F)
-25 °C to 55 °C
(-13 °F to 131 °F)
5% to 95% non-condensing
2g over 10 to 150 Hz; 1g over 150 to 200 Hz
Use
For bolting/mounting the flow computer
For manipulating rotation set screw
For screws on HMI module
For screws on other modules and boards
For optional aluminum enclosure clamps
For 5.08 mm pitch terminal block connections
For installing external solar controller
For installing external solar controller
For installing external solar controller
(D301791X012).
4 1 T
Range
Fiberglass
Enclosure
-35 °C to 80 °C
(-31 °F to 176 °F)
-35 °C to 60 °C
(-31 °F to 140 °F)
-35 °C to 45 °C
(-31 °F to 113 °F)
-25 °C to 55 °C
(-13 °F to 131 °F)
Installation