Commissioning Procedure - Siemens SIMATIC S7-1500 System Manual

Redundant system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Commissioning

12.3 Commissioning procedure

12.3
Commissioning procedure
Requirements
• The CPUs are in the "Factory settings" state or have been reset to factory settings. You can
find more information in the Resetting CPUs to factory settings (Page 466) section.
• The CPUs have the same article numbers.
• The SIMATIC memory cards are as delivered or have been formatted and are not write-
protected.
• The two CPUs of the S7-1500R/H redundant system have the same firmware version. You
can find more information in the Firmware update (Page 461) section.
Procedure for commissioning SIMATIC S7-1500R/H
To commission the S7-1500R/H redundant system, we recommend the following procedure:
Table 12- 1
Procedure for commissioning SIMATIC S7-1500R/H
Step
Procedure
1
Configure hardware in STEP 7
2
Create user program
3
Insert required modules
4
Wire the configuration (lines for supply voltage, PROFINET ring or line
topology, redundancy connections) and check it.
5
Insert SIMATIC memory cards in the CPUs
6
Switch on CPUs, optional system power/load current supply, and dis-
tributed I/O
7
CPU pairing
8
Assign CPUs redundancy IDs
9
Check LEDs
10
Evaluate information on the CPU displays
11
Load hardware configuration and user program to the CPUs
12
Test inputs and outputs
362
More information
Section Configuration (Page 289)
Section Programming the S7-1500R/H
(Page 317) and STEP 7 online help
Section Installation (Page 238)
Section Wiring (Page 258)
Section Removing/plugging in SIMATIC
memory cards (Page 363)
Section First power-on of the CPUs
(Page 366)
Section CPU pairing (Page 366)
Section Redundancy IDs (Page 368)
You can find the meaning of the LEDs in
the module Equipment Manuals.
Section CPU display (Page 434)
Section Downloading projects to the
CPUs (Page 372)
The following functions are helpful:
Monitoring and modifying tags, testing
with program status, forcing, controlling
the outputs in STOP. You can find more
information in the Test and service func-
tions (Page 471) section.
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500r/h

Table of Contents