Use over 2 000 m above sea level and extended
temperature range
C.1

Ambient temperature and installation altitude

Extension of the temperature range and the installation altitude
The previously permissible range of ambient temperature of 0 °C to 60 °C for the horizontal
mounting position has been extended for the R-CPUs to -30 °C to 60 °C (in each case without
condensation or icing).
The accessory components offered for the redundant system (e.g. rails) can also be used
down to -30 °C and for altitudes up to 5 000 m.
The following tables show an overview of the current climatic ambient conditions for
ambient temperature and installation altitude of the R/H-CPUs/displays.
Reference
The current status of the respective R/H-CPUs can be found in the technical specifications
published online.
In general, the module-dependent extended climatic operating conditions are described in
the "Technical specifications" section of the Equipment Manuals for the respective R/H-CPUs.
C.2

CPUs

Redundant CPUs
CPU
CPU 1513R-1 PN
CPU 1513R-1 PN
6ES7513-1RM03-0AB0
CPU 1515R-2 PN
6ES7515-2RM00-0AB0
CPU 1515R-2 PN
6ES7515-2RN03-0AB0
CPU 1517H-3 PN
6ES7517-3HP00-0AB0
CPU 1518HF-4 PN
PFDavg and PFH values for F-CPUs for operating altitudes up to 3 000 m or 5 000 m.
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
Article number
6ES7513-1RL00-0AB0
6ES7518-4JP00-0AB0
Ambient temperature
Temperature
As of
range [°C]
version
0 to +60
FS 01
-30 to +60
FS 01
0 to +60
FS 01
-30 to +60
FS 01
0 to +60
FS 01
0 to +60
FS 01
Installation altitude
Max.
As of
altitude [m]
version
5 000
FS 01
5 000
FS 01
5 000
FS 01
5 000
FS 01
5 000
FS 01
5 000
FS 01