Flash Codes; Resets; Heat Anticipator Setpoints; Start-Up (Cooling) - York WW-15 Installation Manual

Gas/electric single package air conditioners
Table of Contents

Advertisement

175244-BIM-A-0706
6. Auxiliary limit switch (AUX) -
This control is located inside the heat exchanger
compartment and is set to open at 190°F. It is a
manual reset switch. If AUX trips, then the primary
limit has not functioned correctly. Replace the pri-
mary limit.
TABLE 32: LIMIT CONTROL SETTING
Capacity, MBH
Units
(Tons)
Input
15, 20 & 25
300
15, 20 & 25
400
FIGURE 23 - GAS VALVE AND CONTROLS

FLASH CODES

The UCB will initiate a flash code associated with
errors within the system. Refer to UNIT CONTROL
BOARD FLASH CODES Table 35.

RESETS

Remove the call for heating by lowering the thermostat
setting lower than the conditioned space temperature.
This resets any flash codes.

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct.
Too high of a setting will result in longer heat cycles
Unitary Products Group
Limit Control
Opens, ºF
Output
240
195
320
195
and a greater temperature swing in the conditioned
space. Reducing the value below the correct setpoint
will give shorter "ON" cycles and may result in the low-
ering of the temperature within the conditioned space.
TABLE 33: GAS HEAT ANTICIPATOR SETPOINTS
Gas Valve
Honeywell VR8440
White-Rodgers 36C68

START-UP (COOLING)

PRESTART CHECK LIST

After installation has been completed:
1. Check the electrical supply voltage being supplied.
Be sure that it is the same as listed on the unit
nameplate.
2. Set the room thermostat to the off position.
3. Turn unit electrical power on.
4. Set the room thermostat fan switch to on.
5. Check indoor blower rotation.
If blower rotation is in the wrong direction.
Refer to Phasing Section in general informa-
tion section.
Check blower drive belt tension.
6. Check the unit supply air (CFM). See "CHECKING
SUPPLY AIR CFM" on page 45.
7. Measure evaporator fan motor's amp draw.
8. Set the room thermostat fan switch to off.
9. Turn unit electrical power off.

OPERATING INSTRUCTIONS

1. Turn unit electrical power on.
2. Set the room thermostat setting to lower than the
room temperature.
3. First stage compressors will energize after the
built-in time delay (five minutes).
Anticipator Setpoint
1st Stage
2nd Stage
0.30 amp
0.11 amp
53