Muting and override
11-1-5-2 L-activation mode
!WARNING
• The F3S-TGR-CL allows that Muting A or Muting B drop for a maximum
time of 200ms without stopping the muting function. A time longer than
200ms is detected as a muting stop.
SLC
Interrupted
OSSD
Muting
Input A
Muting
Input B
Muting
Status
RT < TM < 120 sec
The L-muting activation mode can be used in applications where material is
transported only out of the dangerous area,
Two muting sensors are connected to the two Muting inputs, Muting A and
Muting B.
This muting activation mode can only be used in uni-directional transport. Fail-
ure to do so may result in serious injury.
DIRECTIONS
ALLOWED
GOODS
DANGEROUS
Note • d1 is the distance between the muting sensors. It must be more than
250mm and needs to be checked additionally in regards to the speed of the
material transport and time limitation in the muting function.
• d2 is the distance between the Muting sensor B and the F3S-TGR-CL sys-
tem. It must be as short as possible. Timing limitations and the speed of the
material transport must be considered additionally.
Free
ON
OFF
ON
OFF
ON
OFF
Active
OFF
< 600s
Mut sen.
Mut sen.
A
B
d1
d
AREA
Section 11-1
F3S-TGR-CL
d2
SAFE
AREA
FENCE
31