Quick Start Guide
Special Conditions for Safe Use (X):
1. When fitted with the transient terminal options, the
equipment is not capable of withstanding the 500 V electrical
strength test as defined in ABNT NBR IEC60079-11. This must
be taken into account during installation.
2. The enclosure may be made from aluminum alloy with a
protective polyurethane paint finish; however, care should be
taken to protect it from impact and abrasion when located in
areas that require EPL Ga (Zone 0).
5.7
China
5.7.1 E3 China Flameproof
Certificate
Standards
Markings
•
产品安全使用特殊条件
证书编号后缀"X"表明产品具有安全使用特殊条件:
1. 涉及隔爆接合面的维修须联系产品制造商。
2. 产品铭牌材质为非金属,使用时须防止产生静电火花,只能用
3. XA 选项时必须配套管以保证实现粉尘防护型式。
4. 产品温度组别和使用环境温度范围之间的关系为:
•
产品使用注意事项
1. 产品外壳设有接地端子,用户在使用时应可靠接地。
2. 安装现场应不存在对产品外壳有腐蚀作用的有害气体。
3. 现场安装时,电缆引入口须选用国家指定的防爆检验机构按检
4. 用于爆炸性气体环境中,现场安装、使用和维护必须严格遵守
24
GYJ21.1277X
GB/T 3836.1-2021, GB/T 3836.2-2021, GB/T 3836.31-2021
Ex db IIC T6···T1 Gb, Ex tb III C T130 °C Db
湿布清理。
过程温度
-60 °C ≤ T
≤ +70 °C
a
-60 °C ≤ T
≤ +80 °C
a
-60 °C ≤ T
≤ +80 °C
a
验认可、具有 Ex db IIC Gb 、 Ex tb IIIC Db 防爆等级的电
缆引入装置或堵封件,冗余电缆引入口须用堵封件有效密封。
"断电后开盖!"的警告语。用于爆炸性粉尘环境中,现场安装、
环境温度
-60 °C ≤ T
≤ +70 °C
a
-60 °C ≤ T
≤ +80 °C
a
-60 °C ≤ T
≤ +80 °C
a
January 2024
温度组别
T6
T5···T1
T130 °C
Rosemount 3144P