Download Print this page

Emerson Rosemount 3144P Quick Start Manual page 13

Temperature transmitters
Hide thumbs Also See for Rosemount 3144P:

Advertisement

January 2024
The following is the minimum configuration requirement for a
temperature measurement. This guide is designed for systems
not using DD methods. For a complete list of parameters
and configuration information, refer to the Rosemount 3144P
Temperature Transmitter
4.2 
Transducer function block
This block contains temperature measurement data for the sensors
and the terminal temperature. It also includes information about
sensor types, engineering units, damping, and diagnostics.
At a minimum, verify the parameters in
Table 4-1: Transducer Block Parameters
Parameter
Typical configuration
SENSOR_TYPE_X
SENSOR_CONNECTIONS_X
Sensor matching configuration
SENSOR_TYPE_X
SENSOR_CONNECTIONS_X
SENSOR_CAL_METHOD_X
SPECIAL SENSOR_A_X
SPECIAL SENSOR_B_X
SPECIAL SENSOR_C_X
SPECIAL_SENSOR_R0_X
4.2.1  Analog Input (AI) function block
The AI block processes field device measurements and makes the
outputs available to other function blocks. The output value of the
AI block is in engineering units and contains a status indicating the
quality of the measurements. Use the channel number to define the
variable that the AI block processes.
At a minimum, verify the parameters of each AI block in
Note
All devices ship with the AI blocks scheduled, meaning the operator
does not need to configure the block or he or she uses factory
default channels.
Quick Start Guide
Reference
Manual.
Table
Comments
Example: "Pt 100_A_385 (IEC 751)"
Example: "2-wire", "3-wire", "4-wire"
"User Defined, Calvandu"
Example: "2-wire", "3-wire", "4-wire"
Set to "User Trim Standard"
Enter sensor specific coefficients
Enter sensor specific coefficients
Enter sensor specific coefficients
Enter sensor specific coefficients
Quick Start Guide
4-1.
Table
4-2.
13