D V P - E S 2 / E X 2 / E C 5 / S S 2 / S A2 / S X 2 / S E & T P O p e r a t i o n M a n u a l - P r o g r a m m i n g
CR number
Attribute
HW
LW
#89
#88
R/W
IP address
#91
#90
R/W
Netmask
#93
#92
R/W
Gateway IP address
Enabling the setting of
#94
R/W
an IP address
Status of setting an IP
#95
R
address
#101~#96
-
Reserved
#102
R/W
MC Protocol UDP port
#110~#103
-
Reserved
#111
R/W
8-bit processing mode
MODBUS TCP
#112
R/W
Keepalive time
#113
-
Reserved
#114
R/W
MODBUS TCP timeout
#115
R/W
MODBUS TCP trigger
#116
R/W
MODBUS TCP status
MODBUS TCP
#118 #117
R/W
destination IP
MODBUS TCP data
#119
R/W
length
MODBUS TCP data
#219~#120
R/W
buffer
#248~#220
-
Reserved
#251
R
Error code
#255~#252
-
Reserved
Symbols "R" refers to "able to read data by FROM instrcution"; "W" refers to "able to write data by
TO instrcution".
B.2.4 DVP-FEN01 (DVP-EH3 Series Ethernet Communication Card)
CR number
Attribute
HW
LW
#0
R
Model code
#1
R
Firmware version
#2~#12
-
Reserved
Enabling the data
#13
R/W
exchange
#16~#14
-
Reserved
#17
R/W
Execution cycle of the data exchange (ms)
B - 6
DVPEN01-SL Ethernet communication module
Register name
Setting an IP address
One CR takes two bytes, and the decimal number
should convert to hexadecimal one.
Setting a netmask
One CR takes two bytes, and the decimal number
should convert to hexadecimal one.
Setting a gateway IP address
One CR takes two bytes, and the decimal number
should convert to hexadecimal one.
Executing the setting of an IP address
Showing the status of setting an IP address
0: The setting of an IP address is successful.
1: The setting of an IP address fails.
Setting the UDP port of an MC protocol data
exchange slave (Default value: 1025)
Setting up MODBUS TCP Master control as 8-bit
mode
MODBUS TCP Keepalive time (Unit: Second)
Setting up MODBUS TCP timeout (Unit:
Millisecond)
Setting up whether to send out data in MODBUS
TCP mode
Displaying current status of MODBUS TCP mode
Setting up destination IP address for MODBUS
TCP transaction
Setting up the data length for MODBUS TCP
transaction
Data buffer of MODBUS TCP for storing
sending/receiving data
Displaying the errors. See the error code table for
more information.
DVP-FEN01 Ethernet communication card
Register name
Description
Description
The model code of DVP-FEN01 is set by its
system, and can only be read. It is H'6151.
It adopts the hexadecimal system, and the
present firmware version is stored in it.
Users can set CR#13 to "sending the data" or
"not sending the data".