INSTALLATION INSTRUCTIONS
WARNING: This installation must be performed by a technically competent person. To prevent injury, damage or malfunction,
read the following instructions carefully. If in doubt, contact your representative for further advice.
WARNING: Make sure electrical power is isolated from the system before installing or opening the product.
WARNING: Consider system requirements and earth the enclosure to prevent electrostatic charge build up.
WARNING: Modifications not described in these instructions will void product certifications.
WARNING: The equipment is to be installed only in areas where there is a low risk of impact.
WARNING: Suitably pre-certified blanking plugs or cable glands must be used with an ingress protection rating of IP65.
For ATEX applications, suitable pre-certified M20 and M25 blanking elements and cable glands are to be selected by either the
manufacturer or end-user for use with the enclosure ensuring the COT is within the permitted range and the ingress protection
rating (IP65) of the enclosure is to be maintained and that these blanking elements and cable glands shall be certified to the same
standards editions to which the enclosure is certified. Refer to the Declaration of Conformity.
WARNING: The hose together with its associated connection arrangement used to connect between each DP bulkhead connector on
the exterior of the equipment and the system with which it is associated, shall be selected by the end user.
For ATEX applications, the hose and its selected connection arrangement shall be made from a suitable material to ensure that there
is not an electrostatic risk or other risk introduced. The permitted medium into the enclosure via each DP bulkhead connector shall
be clean, dry, dust-free air or inert gas, with a maximum pressure of 45 mbar [4.5 kPa] and a maximum temperature of 50°C. The
hose, and its associated connection arrangement, shall be suitable for the conditions of use to which it will be subjected in service
and ensure that a degree of ingress protection IP65 is maintained at all times.
STEP 1
ISP12
ISP20/40
Carefully mount board
For boards supplied in a polycarbonate enclosure, mount the enclosure
securely using mounting points on the enclosure. Mount either horizontally
(cover faces up) or vertically (so writing on the board is the correct way up).
©COPYRIGHT Goyen Controls Co. Pty. Ltd.
PRODUCT INSTALLATION INSTRUCTIONS
For boards supplied in a polycarbonate enclosure
IS/ISP20/40
278.0 [10.94"]
254.0 [10.00"]
188.0 [7.40"]
164.0 [6.46"]
IS/ISP12
Mount the enclosure securely using mounting points on the enclosure.
Mount either horizontally (cover faces up) or vertically (so writing on the
board is the correct way up).
4/56
GOYEN IS/ISP SERIES CONTROLLER
DEINE-012
130.0 [5.12"]

Advertisement