Operation Of The Controller - Pentair GOYEN IS Series Products Installation Instructions

Advertisement

dP Units *
Press Select
when the 'dP Units' LED is lit.
This LED should start to flash indicating it is in programming mode.
Use the Up
and Down
buttons to select a the dP Units in either
kPa or InWG.
Press Select
to confirm the setting. The 'dP Units' LED should now be lit.
Press Down
to scroll down the list.
High dP Alarm *
Press Select
when the 'dP Units' LED is lit.
This LED should start to flash indicating it is in programming mode.
Use the Up
and Down
buttons to set the value that will trigger
the High dP Alarm in the event the dP rises above this setting.
(Min. 00.0–Max. 18.0)
Press Select
to confirm the setting. The 'High dP Alarm' LED should
now be lit.
Press Down
to scroll down the list.
On Time
Press Select
when the 'On Time' LED is lit.
This LED should start to flash, indicating it is in programming mode.
Use the Up
and Down
buttons to select an On Time in
miliseconds between 30 ms and 990 ms, in increments of 10 ms.
Press Select
to confirm the setting.
Note: A standard setting is 150–250 ms.
Note: The Off Time must allow each solenoid to have a 60-second rest between
pulses.
Off Time
Press Select
when the 'Off Time' LED is lit.
This LED should start to flash, indicating it is in programming mode.
Use the Up
and Down
buttons to select an Off Time in seconds
between 1 s and 999 s.
Press Select
to confirm the setting.
Note: The Off Time must allow each solenoid to have a 60-second rest between
pulses.
* ISP only
©COPYRIGHT Goyen Controls Co. Pty. Ltd.
PRODUCT INSTALLATION INSTRUCTIONS
Blowdown Cycles
Press Select
when the 'Blowdown Cycles' LED is lit.
This LED should start to flash, indicating it is in programming mode.
Use the Up
and Down
cycles you require, between 0 and 10.
Press Select
to confirm the setting.
Note: Blowdown cycles can only be triggered by the Fan Stop Input.
Run
Press Select
when the 'Run' LED is lit.
This will automatically exit Programming Mode and save your settings.
WARNING: This installation must be performed by a
technically competent person. To prevent injury, damage
or malfunction, read the following instructions carefully.
If in doubt, contact your representative for further advice.

OPERATION OF THE CONTROLLER

On power up, the controller will automatically detect how many pilot valves
are connected and display FXX, where XX will be the number of pilot valves
found.
When the controller is running in continuous mode the screen will display
the next valve that will be pulsed.
When the controller is running in demand mode the screen will display the
dP reading and briefly flash the next valve that will be pulsed.
OUTPUTS AND ALARMS
The screen will display "FSP" when a fan stop event is triggered, i.e. when
this input is closed circuit. It will automatically clear when this event has
cleared, i.e. when this input is open circuit.
The screen will display "LoH" when a low header event is triggered, i.e.
when this input is closed circuit. It will automatically clear when this even
has cleared, i.e. when this input is open circuit.
The screen will display "-|XX" when there is a short circuit event on a pilot
valve and "oXX" when there is an open circuit event on a pilot valve, where
XX is the output number of the pilot valve effected. It will automatically
clear once either fault has been fixed.
REPLACEMENT FUSE INFORMATION
MANUFACTURER
PART NUMBER
Bel Fuse
5MF 3-R
Bel Fuse
5ET 1-R
Bel Fuse
5ET 2.5-R
3/56
GOYEN IS/ISP SERIES CONTROLLER
DEINE-012
buttons to select the number of blowdown