Installation, Operation and Maintenance Manual
FCIM-20054-EN Rev. 0
Section 7: Settings
The following additional parameters become visible in the control unit for the
Bettis RTS electric actuator with the PROFINET option enabled.
Table 3.
P15.1
P15.2
P15.3
P15.4
P15.5
P15.6
P15.7
P15.8
P15.9
P15.10
P15.11
NOTE:
After changing parameters P15.1 to P15.3, the protocol stack for the PROFINET is restarted to apply
the change.
NOTE:
To allow the actuator to be unambiguously identified in the network, the MAC
address is displayed in the bottom most line of Status Area S5.
Settings
Additional Parameters
Menu
Sub Menu
Poss. Setting
Item
Item
0: Not Activated 0: Not Activated
Bus
1: Activated
1: Activated
Bus
0 to 255
0 to 255
Bus
0 to 255
0 to 255
Bus
0 to 255
0 to 255
0
0
1
1
Bus
2
2
3
3
Watchdog
0.0 to 10.0 s
Bus
Time
(0.0 s)
(0):
Setpoint
1: Analog
Bus
Source
2: Bus/analog
(0)
Bus
Status 2
1 to 2
(0)
Bus
Status 3
1 to 2
(0)
Bus
Status 4
1 to 2
0: Ignore
1: Stop
2: Open
3: Close
Bus
Bus
4: Emergency Position -
Monitor
5: Emergency Open
6: Emergency Close
7: Last valid value
8: Fail-safe
Section 7: Settings
Notes/Comments
PROFINET disabled
PROFINET enabled
Valid IP address
Valid net mask
Valid gateway
Off
Swap In/Off
Swap In
Swap Out
Monitoring of the toggle bit transmitted from the master
(bit 7 in the command). With a bus watchdog time set, this
bit has to toggle within that time; otherwise there is a bus
watchdog fault. At 0.0 s the watchdog function is disabled,
in which case toggling of the toggle bit may be omitted.
The set point is specified via the PROFINET (only relevant
when the positioner is enabled).
The set point is specified by the analogue signal (only
relevant when the positioner is enabled).
With an error-free bus, the set point is specified via
the PROFINET. With a bus error, the analogue value is
switched to (only relevant when the positioner is enabled).
Standard assignment for Status 2.
Reserved for future use.
Standard assignment for Status 3 (current event).
Reserved for future use.
Standard assignment for Status 4 (current event).
Reserved for future use.
-
-
-
-
-
-
-
-
September 2023