Recommended Nozzles; Maintenance Position - Riello Gulliver RG1 Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

4.
WORKING
4.1 COMBUSTION ADJUSTMENT
In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and
testing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO
concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the setting of
the combustion head, and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO 2 at sea level and with light oil and room temperature of 20 °C
Nozzle
GPH
Angle
0.65
60°
0.75
60°
0.85
60°
1.00
60°
1.10
60°
1.10
60°

4.2 RECOMMENDED NOZZLES:

For ignitions at low temperature (lower than + 8 °C) act as follows:
Use nozzles with empty or half-empty cone of
the following type:
Delavan type W ;
Monarch type NS ;
or (as alternative) increase the pump pressure
up to 14 bar.
If necessary, adopt both solutions.

MAINTENANCE POSITION

THE ACCESSIBILITY TO THE NOZZLE, THE
DIFFUSER DISC AND THE ELECTRODES IS
MADE EASY IN 2 WAYS:
A
Fig. 10
Remove the burner out of the boiler, after loos-
ing the fixing nut to the flange.
Hook the burner to the flange (1), by remov-
ing the blast tube (2) after loosing the fixing
screws (3).
Remove the small cables (4) from the elec-
trodes and the diffuser disc-holder assembly (5)
from the nozzle-holder assembly after loosing
its fixing screw (3, fig. 12, page 7).
Screw the nozzle (6) correctly and tighten it
as shown in the figure.
20024093
Pump
pressure
bar
12
12
12
12
12
15
Delavan type W - B ; Danfoss type S - B - H
Monarch type R - NS ; Steinen type S - Q - H
Danfoss type H;
Steinen type H,
Burner
Combustion head
output
adjustment
kg/h ± 4%
Set-point
2.7
3.0
3.4
4.0
4.4
5.0
2
5
4
6
GB
.
Air damper
adjustment
Set-point
2.5
3
3.5
4
4
4
A
Fig. 10
3
6
2
1.5
2.9
4.2
5.6
6.3
6.7
1
S7477

Advertisement

Table of Contents
loading

This manual is also suitable for:

363 t1

Table of Contents