4. Capacity Table
Hydro Unit HT
2) Capacity calculation method
How to calculate heating capacity power input : Combination of outdoor unit and hydro unit HT
- Heating c apacity and power input of hydro unit HT : refer to the indoor unit capacity table.
- Power input of outdoor unit : refer to the Outdoor unit capacity table (indoor 68℉ DB).
Example
- Standard condition : Outdoor 44.6℉ DB/42.8℉ WB, Indoor 68℉ DB
- Water condition : EW 55℉, LW 65℉
6TON DVM S TDB Heat Capacity Table
Combination,%
(Capacity index)
100%
Combination 1 (Outdoor Unit 6TON + Indoor Unit 6TON)
Indoor Heat Capa.[Btu/h ]
PI Indoor Unit(6TON)[kW]
PI Outdoor Unit(6TON)[kW]
PI System[kW]
Outdoor Temperature(℉)
DB
-4
1
5
10
14
19
23
27
32
37
41
45
48
52
55
59
86,000
= HT Capacity Table
3.831
= HT Capacity Table (Ref. P.17)
5.10
8.93
=Indoor Unit PI + Outdoor Unit PI
Indoor Temperature(℉,DB)
TC
WB
Btu/h
-6
67,560
0
71,314
3
75,067
9
78,138
12
81,550
18
83,256
21
85,986
25
85,986
30
85,986
36
85,986
39
85,986
43
85,986
46
85,986
50
85,986
54
85,986
57
85,986
68℉
PI
kW
7.8
7.96
8.04
7.92
7.68
7.21
6.84
6.21
5.84
5.52
5.23
5.1
4.85
4.63
4.42
4.27