Counter N A, Counter N B, And Counter N Z Signals; Routing Signals To A, B, And Z Counter Inputs; Routing Counter N Z Signal To An Output Terminal; Counter N Up_Down Signal - National Instruments PXI-6238 User Manual

Isolated current input/current output devices
Table of Contents

Advertisement

In addition, Counter 1 Internal Output, Counter 1 Gate, Counter 1 Source,
or Counter 0 Gate can be routed to Counter 0 Aux. Counter 0 Internal
Output, Counter 0 Gate, Counter 0 Source, or Counter 1 Gate can be routed
to Counter 1 Aux.
Some of these options may not be available in some driver software.

Counter n A, Counter n B, and Counter n Z Signals

Counter n B can control the direction of counting in edge counting
applications.
Use the A, B, and Z inputs to each counter when measuring quadrature
encoders or measuring two pulse encoders.

Routing Signals to A, B, and Z Counter Inputs

Each counter has independent input selectors for each of the A, B, and Z
inputs. Any of the following signals can be routed to each input.

Routing Counter n Z Signal to an Output Terminal

You can route Counter n Z out to RTSI <0..7>.

Counter n Up_Down Signal

Counter n Up_Down is another name for the Counter n B signal.

Counter n HW Arm Signal

The Counter n HW Arm signal enables a counter to begin an input or output
function.
To begin any counter input or output function, you must first enable, or arm,
the counter. In some applications, such as buffered semi-period
measurement, the counter begins counting when it is armed. In other
applications, such as single pulse-width measurement, the counter begins
© National Instruments Corporation
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
ai/StartTrigger
PXI_STAR
RTSI <0..7>
Input PFI <0..5>
PXI_STAR
7-29
Chapter 7
Counters