6 - OPERATION

6.3 - Safety functions

Compressor protection device
CARRIER industrial heat pumps are equipped with a protection 
device  for  the  screw  compressor  as  standard.  The  protection 
device is installed in the compressor terminal box.
Safety monitoring by the compressor protection device:
■ Temperature monitoring
The  compressor  protection  device  locks  out  as  soon  as  the 
highest permissible motor or oil temperature is exceeded.
■ Rotational direction monitoring
The  compressor  protection  device  monitors  the  rotational 
direction in the first 5 seconds after the compressor has started. 
If the compressor starts in the wrong direction, the protection 
device  locks  out  immediately.  In  addition,  CARRIER  uses  a 
second, upstream rotational direction monitor, which prevents 
the compressor starting in the wrong direction in advance.
■ Phase failure monitoring
In the event of a phase failure within the first 5 seconds after 
the compressor has started, the protection device immediately 
opens the relay contact in the safety chain and closes it again 
after 6 minutes. It fully locks out after 3 phase failures inside 
18 minutes or after 10 phase failures within 24 hours.
16
Further safety equipment:
■ Motor overload relay for the compressor
■ Motor overload relay for the required source pump 
■ Motor overload relay for the required condenser pump 
■ High and low pressure controller 
■ High and low pressure sensors
■ Hot gas temperature monitor 
■ Frost protection monitor 
■ Differential pressure switch at the evaporator 
■ Flow  switch  for  the  evaporator  is  optionally  available  and  is 
recommended  by  CARRIER  for  low  evaporator  inlet 
temperatures. 
■ Differential pressure switch for filter in the oil circuit
Safety valve:
A safety valve discharge pipe must discharge the refrigerant to 
the ambient air or to removal devices in a suitable manner or direct 
it into absorbent material available in an adequate amount. The 
refrigerant must not be directed into adjacent rooms, stairwells or 
similar. The refrigerant must not be brought into contact with an 
air supply for combustion engines, boilers or air compressors. 
If for improved service quality a sealed ball shut-off valve is fitted 
upstream of the safety valve on the condenser, note the following: 
as soon as the valve service has been completed, the ball shut-off 
valve must be checked while in the open position and sealed by 
a  qualified  inspection  body  in  accordance  with  the  Pressure 
Equipment Directive 2014/68/EU.