Fitting Sensor Leads - Carrier 61CW-Z Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

4 - INSTALLATION
Max. operating
Heat pump type
current, compressor
61CW-Z 392
61CW-Z 472
61CW-Z 572
61CW-Z 742
C
The cable cross-sections listed in Table 2 apply to a cable length 
of up to 50 m at an ambient temperature not exceeding 30 °C. In 
each case, the electrician responsible must ensure appropriate 
sizing.
The power cables must be used to create a clockwise rotating
field. The clockwise rotating field must be ensured before
commissioning.
Caution: Operation with the wrong rotational direction will
result in compressor damage.
DANGER! Connection work which requires electrical
distributors to be opened must be carried out by authorised
electricians, since there is a risk to life when working on live
components.
Observe the accident prevention regulations.
CAUTION! Only CARRIER customer service may start the
heat pump for the first time.
12
Power cable
protection
(selectivity 1:1.6)
295A
LV HRC 400 A
361A
LV HRC 500 A
428A
LV HRC 500 A
551A
LV HRC 630 A
Fig. 2
B
D
8 mm
31 Nm
(274 lb-in)
Table 2
Torque of
terminal screw
M10 - 31 Nm
M10 - 31 Nm
M10 - 31 Nm
M10 - 31 Nm

4.8 - Fitting sensor leads

Route  sensor  leads  in  separate  conduits  or  preferably  use 
screened  leads  to  avoid  induction  and  resulting  controller 
malfunction.
If installing an outdoor temperature sensor for the controller, fit it 
at a height of about 2.5 m on an outside wall of the building (north-
west side). Make sure that the temperature sensor is not exposed 
to direct sunlight or wind, as this will impair the control behaviour.
Caution: Never apply voltage to sensor terminals. (Destruction
of the controller).
Single core copper
Copper power cable,
power cable,
minimum cross-
minimum cross-
section up to 50 m
section up to 50 m
4 x 240 mm²
4 x 185 mm²
2 x 4 x 95 mm²
2 x 4 x 70 mm²
4 x 300 mm²
4 x 24 mm²
2 x 4 x 120 mm²
2 x 4 x 95 mm²
 4 x 300 mm²
 4 x 240 mm²
2 x 4 x 120 mm²
2 x 4 x 95 mm²
2 x 4 x150 mm²
2 x 4 x120 mm²

Advertisement

Table of Contents
loading