Flue Terminal Positions - Worcester Greenstar 1000 GR1000W 24 C NG Installation And Maintenance Instructions Manual

Gas-fired condensing combi appliance
Table of Contents

Advertisement

Pre-Installation
WARNING
Minimum plume management length:
The minimum distance of 500mm must be maintained between air inlet
and exhaust outlet.
▶ Do not terminate the plume management inside the terminal
exclusion zone (shaded area) shown in figure 27.
≥140mm
m m
0 0
≥ 5
m
0 m
5 0
m
0 m
5 0
Fig. 27 Terminal exclusion zone
NOTICE
Cutting the 500mm pipe
▶ The Plume management extension kit contains the components
required for such a configuration.
20
100mm
X
5 0
0 m
±80°
m
0010013548-003
Plume management bends
NOTICE
Effective plume management lengths of bends:
Each bend used has an equivalent straight plume management length.
▶ Refer to the table 16.
Bend
Effective plume management length
45°
90°
Table 16 Effective length of bends
For every extra 1,000mm of plume management after the first 500mm,
the internal 60/100 flue length must be reduced by 700mm, up to a
maximum of 4,500mm of plume management.
2,800
2,100
1
1,400
[mm]
700
0
500
1,500
Fig. 28 Reduction to flue length as plume length increases graph
[1]
Reduction to flue length [mm] (maximum reduction 2,800mm)
[2]
Plume length [mm] (maximum plume length 4,500mm)
4.4.4

Flue terminal positions

CAUTION
Flue terminal positions
▶ All measurements are the minimum clearances required.
▶ Terminals must be positioned so to avoid combustion products
entering the building.
Greenstar 1000 – 6721835943 (2023/08)
0.75 metres
1.5 metres
2,500
3,500
4,500
2
[mm]
0010023114-001