Worcester Greenstar 1000 GR1000W 24 C NG Installation And Maintenance Instructions Manual page 29

Gas-fired condensing combi appliance
Table of Contents

Advertisement

Open drain or gully with external air break
 Figure 37
Where the pipe terminates over an open drain or gully and there is a risk
of ground flooding, then the additional requirement below is
recommended:
• An air break should be installed in the external pipework as shown to
avoid an airlock during ground flooding/adverse weather conditions
which could prevent the condensate from discharging.
1
21
8
Fig. 37 Disposal to open drain or gully with air break
[1]
Condensate discharge from appliance
[8]
Pipework transition
[9]
Additional protection for transition through a wall.
[11] External air break
[21] Increase pipe size
Condensate soak away considerations
Before deciding to use a purpose-made soak away the history of the
locality and the ability of the surrounding area to disperse the
condensate should be taken into account, e.g. areas prone to flooding
and ground with a high clay content can result in poor drainage with an
increased risk of water logging or freezing causing the condensate pipe
to become obstructed by water or ice and the boiler to shut down,
Although it is possible to increase the size of the soak away and the area
with limestone chippings in clay soil areas, if the clay content is high and
prevents effective dispersal of the condensate then a soak away may not
be a suitable means of condensate disposal and an alternative method
should be used.
Condensate soak away with external air break
 Figure 38
• Refer to following example to dispose of condensate to a soak away.
• The condensate soak away must be sited at least 500mm away from
building footings.
• The condensate drainage pipe may be run above or below the ground
to the soak away. The following example shows drainage pipe run
above ground.
• The soak away must use a minimum of a 100mm Ø plastic tube with
two rows of three 12mm holes on 25mm centres and 50mm from the
bottom of the tube. The holes must face away from the house.
• The tube must be surrounded by at least 100mm of limestone
chippings to a depth of 400mm.
• An air break must be installed in the external pipework as shown to
avoid an airlock during ground flooding/adverse weather conditions
which could prevent the condensate from discharging.
Minimum hole size for the condensate soak away must be 400mm deep
by Ø 300mm.
Greenstar 1000 – 6721835943 (2023/08)
9
11
21
25mm min.
9
1
8
15
16
Fig. 38 Disposal to soak-away
[1]
Condensate discharge from appliance
[8]
Pipework transition
[9]
Appliances with small capacity trap without CondenseSure
accessory fitted.
[11] External air break
[15] 100mm minimum Ø plastic pipe
[16] Drainage holes
[17] Limestone chippings
[18] Bottom of sealed tube
[19] Increase size of soak away size and the area with limestone
chippings if in clay soil area.
Not recommended for high clay soil areas.
[21] Increase pipe size
Minimum Standard
▶ The following guidance indicates the minimum standards that must
be maintained for the Installation and Maintenance of a product.
Appliances with small capacity trap without CondenseSure
accessory fitted.
All external pipework must be insulated using suitable waterproof and
weather resistant insulation.
External pipework exceeding three metres in length.
▶ One of the following must be installed:
▶ Trace heating,
-or-
▶ A condensate pump,
-or-
▶ A CondeseSure accessory.
Trace heating fitted:
• Check with trace heating manufactures instructions for additional
requirements.
Pre-Installation
400mm min.
25mm min.
500mm min.
21
11
21
15
16
19
17
18
0010012788-002
29