17.3.3 1-group linked-control system

17.3.4 Linked control with more than 2 groups

Installer and user reference guide
76
b Slave controller for VAM
c Switch position: Master
d Switch position: Slave
e Maximum length of connection line: 500 m
VAM VAM heat reclaim ventilation unit
NOTICE
Factory settings: Do NOT change the switch settings when a controller is connected.
SS1 is a setting switch to operate the unit without controller. Changing the switch
setting when a controller is connected will stop the unit from operating normally.
Keep the switch on the PCB in the factory setting position.
NOTICE
Group control connection is NOT allowed.
NOTICE
Group control connection is NOT allowed with EKVDX indoor units.
The air conditioner's controller can be used to control up to 16 units, a
combination of indoor air conditioner units and heat reclaim ventilation units.
You can configure initial settings for the functions of the VAM units. These
functions are precool/preheat, ventilation air flow, ventilation mode, and fresh-
up. Use the air conditioner's controller to configure the initial settings for the
VAM units. See
"17.2 Field
VRV
P1
P2
a Controller for air conditioner
b Controller for air conditioner
c Maximum length of connection line: 500 m
VRV VRV indoor unit
VAM VAM heat reclaim ventilation unit
NOTICE
Group control connection is NOT allowed with EKVDX indoor units.
To change the settings, P1/P2 of the controller MUST be connected to the VAM
units. The controller can be removed after the settings are changed.
If the unit is supposed to operate without controller, do NOT switch it on with the
controller connected. Otherwise, the unit will give an error once the controller is
removed, because it will keep on searching for the controller signal. To resolve the
error, perform a power reset without the controller connected.
The optional adapter PCB (KRP2A51) must be connected to 1 unit that is part of
the F1/F2 loop. This unit can be an air conditioner or a VAM unit.
4
settings" [
 72].
VAM
P1 P2
c
P1P2
P1 P2
a
b
VAM350~2000J*VEB*
Heat reclaim ventilation unit
4P664012-1A – 2024.01