3
|

Specific installer safety instructions

3 Specific installer safety instructions
Installer and user reference guide
12
Always observe the following safety instructions and regulations.
Unit installation (see
"14 Unit
WARNING
Fixing method of the heat reclaim ventilation unit MUST be in accordance with the
instructions from this manual. See
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
This unit is suitable for installation in a commercial and light industrial environment.
WARNING
When connected to an EKVDX, the height of the air extraction opening from the
room MUST be be equal or below the refrigerant release point.
CAUTION
The appliance is designed to be a built-in appliance. It may NOT be accessible to
the general public. Adequate measures have to be taken to prevent access by
other than qualified persons.
Check if the installation location can support the unit's weight. Poor installation is
hazardous. It can also cause vibrations or unusual operating noise.
Provide sufficient service space and inspection holes. Inspection holes are needed
for the air filters, the heat exchange elements and the fans.
Do NOT install the unit so that it is in contact with a ceiling or wall, this may cause
vibration.
CAUTION
A minimum length of 1.5 m is required for the outdoor air, exhaust air and return
air ducting. If the ducting is shorter, or if no ducting is installed, then you MUST
install grilles in the duct openings or the openings of the unit.
Make sure no wind can blow in the ducting.
WARNING
When combined with an EKVDX unit, do NOT install operating ignition sources
(example: open flames, an operating gas appliance or an operating electric heater) in
the duct work.
Electrical installation (see
WARNING
Electrical wiring connection method MUST be in accordance with the instructions
from this manual. See
4
installation" [
 42])
"14.4 To install the anchor
"15 Electrical
installation" [
"15 Electrical
installation" [
4
bolts" [
 47].
4
 50])
4
 50].
VAM350~2000J*VEB*
Heat reclaim ventilation unit
4P664012-1A – 2024.01

Advertisement

Table of Contents
loading

Table of Contents