Danfoss ECtemp Next Plus Installation Manual page 16

Electronic intelligent timer thermostat
Hide thumbs Also See for ECtemp Next Plus:
Table of Contents

Advertisement

Press M button for 6 seconds
Select P03 (Table in 4.2): raise oor temperature limitation
4.11 Table for 4.9 Change to Room control only and
4.10 Extending Maximum Floor temperature
limitations to 45°C
No.
Function
P01
Room Sensor
Calibration
P02
Floor Sensor
Calibration
P03
Maximum
Room Temp.
Limitation
P04
Minimum
Room Temp.
Limitation
P05
Maximum
Room Temp.
Limitation
P06
Minimum
Room Temp.
Limitation
P07
Setting range
extension for
P06, P07, P08
16
Danfoss ECtemp Next Plus
higher than 35°C by using the >
Setting
O set:-10˚C to
+10˚C
O set:-10˚C to
+10˚C
5-35˚C(Active in
Temperature Control
Mode 01)
5-35˚C(Active in
Temperature Control
Mode 01)
5-35˚C(Active in
Temperature Control
Mode 02)
5-35˚C(Active in
Temperature Control
Mode 02)
01: Max. 35˚C, 02:
Max. 45˚C
Factory default
Danfoss ECtemp™
Next Plus
0˚C
0˚C
35˚C
5˚C
35˚C
5˚C
01
Installation Guide