Operation

7.3 Shut Down the System

1
If the system is on, press the inverter POWER button for 1 second to turn off the
inverter.
2.
Switch off the PV DC switch of the inverter (turn to ""OFF" position).
3.
Press the battery POWER button to turn off the battery.
4.
Switch off the circuit breaker of the battery.
Switch off the AC circuit breakers for the EV-SB and inverter.
5.

7.4 Definition of indicator light and button

Fault LED 1 and Fault LED 2
LED1 flashes green (0.5s on, 0.5s off) and LED2 is red when arc
fault occurs. (Arc Detect Fault)
LED1 flashes green (2s on, 2s off) and LED2 is red when ground
fault occurs. (Isolation Fault)
LED1 flashes green (0.5s on, 0.5s off) and LED2 is off when PV
voltage fault occurs.(PV Volt Fault)
LED1 flashes green (2s on, 2s off) and LED2 is off when Grid
error occurs. (GridUnderVoltFault / GridOverVoltFault /
GridUnderFreqFault / GridOverFreqFault)
LED1 flashes green (0.5s on, 0.5s off) and LED2 flashes red
(0.5s on, 0.5s off) when firmware upgrading is ongoing.
LED1 is green and LED2 is red when other fault occurs.
LED1 is off and LED2 is off when no fault occurs.
64
Operation LED (Free / Secondary)
Green when the inverter is in normal status or in backup
status.
Flashing green (1s on, 1s off) when the inverter is in waiting
or checking status.
Off when the inverter has a fault.
Operation LED (Primary)
Green for 2s and then quick flashing green for 1s (0.2s on,
0.2s off) when the inverter is in normal or backup status.
Flashing green for 2s (1s on, 1s off) and then quick flashing
green for 1s (0.2s on, 0.2s off) when the inverter is in waiting
or checking status.
Off for 2s and quick flashing green for 1s (0.2s on, 0.2s off)
when the inverter has a fault.
BAT LED
Green when the battery communication is normal and working.
Flashing green (1s on, 1s off) when the battery
communication is normal and the battery is in idle status.
Off when the battery does not communicate with inverter.
All LEDs
All LEDs flash (0.5s on, 0.5s off) when firmware upgrading has been
completed but the U drive is still connected.
All LEDs will be back to the normal state if the U drive is unplugged
after the upgrading finished.
Inverter power button
Press the button for 0.5 second: Clear EPS OverLoad Fault / EPS Bat
Power Low / BI_TransformerImbalanceHighFault /
BI_VoltImbalanceFault / BatBreakOpen Fault.
Press the button for 1 second: Turn on the inverter if it has been turned
off.
Press the button for 1 second: Turn off the inverter if it has been turned
on. The control circuitry remains powered up.
Press the button for 5 seconds: Run arc self-test if there is no arc fault.
Press the button for 5 seconds: Clear arc fault if arc fault occurs.
Operation
65