4.3.5

Installation and position of any obstacles

OBLIGATION:
The air expelled from the machine must be easily dispersed into the environment. Avoid the presence
of obstacles that may cause the expelled air to recirculate.
Structures around the installation perimeter must ensure the free movement of air such as: finned
barriers, finned barriers with sound-proofed passages. There are no height limits for finned barriers.
Masonry barriers must not exceed a height of 1200 mm.
Perimeter structure with
A very high masonry structure is
allowed, but at least one very wide
finned barrier must be present
IT IS FORBIDDEN TO SURROUND
THE INSTALLATION WITH A
MASONRY BARRIER WITH A
HEIGHT OF MORE THAN 1200 MM.
Installation, use and maintenance manual
finned barriers.
No height limit.
Masonry perimeter structure with
a height limit of 1200 mm.
Masonry perimeter structure with a height
limit of 1200 mm.
The finned barrier can protrude over the
masonry.
AVOID INSTALLING THE
MACHINE IN THE DISCHARGE
AIR FLOW OF ANY
EXTRACTORS.