Lennox A97DF2E Installation Instructions Manual page 19

Warm air gas furnace downflow air discharge direct vent & non-direct vent
Table of Contents

Advertisement

Maximum Allowable Exhaust Vent Lengths Using Ventilated Attic or Crawl Space for Intake Air in Feet
1-1/2" Pipe
Number
of 90°
Model
Elbows
45
70
Used
1
15
10
2
10
3
4
5
6
n/a
n/a
7
8
9
10
NOTE: Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
508391-01
Standard Termination at Elevation 0 - 10,000 ft
90
110
45
70
56
41
51
36
46
31
41
26
36
21
n/a
n/a
31
16
26
21
16
11
n/a
Pipe size determined in table 7.
2"
2"
2"
2"
or
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2" PVC pipe possible.
NOTE: Exhaust pipe and intake pipe must be the same diameter.
Figure 23. Typical Exhaust Pipe Connections
2" Pipe
Model
90
110
45
24
85
19
80
14
75
9
70
4
65
n/a
60
11
55
6
n/a
50
1
45
40
Table 7C.
2"
3"
TRANSITION
*2"
DO NOT transition
from larger to smaller
pipe in horizontal runs
of exhaust pipe.
Issue 2327
2-1/2" Pipe
Model
70
90
110
45
85
63
28
103
80
58
23
98
75
53
18
93
70
48
13
88
65
43
8
83
60
38
3
78
55
33
73
50
28
68
n/a
45
23
63
40
18
58
NOTE: 1-1/2" Vent Pipe
Diameter Allowed Only
on 045/070 Units
1-1/2"
or
TRANSITION
*2"
INTAKE
3" Pipe
Model
70
90
110
102
83
83
97
78
78
92
73
73
87
68
68
82
63
63
77
58
58
72
53
53
67
48
48
62
43
43
57
38
38
EXHAUST
TOP VIEW
Page 19 of 52