Lennox A97DF2E Installation Instructions Manual page 16

Warm air gas furnace downflow air discharge direct vent & non-direct vent
Table of Contents

Advertisement

1.
In areas where piping penetrates joist or interior walls,
hole must be large enough to allow clearance on all
sides of pipe through center of hole using a hanger.
2.
When furnace is installed in a residence where unit
is shut down for an extended period of time, such
as a vacation home, make provisions for draining
condensate collection trap and lines.
Exhaust Piping
Route piping to outside of structure. Continue with
installation following instructions given in piping termination
section.
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical
discharge through an existing unused stack is required,
insert PVC pipe inside the stack until the end is even
with the top or outlet end of the metal stack.
The exhaust vent pipe operates under positive pressure
and must be completely sealed to prevent leakage of
combustion products into the living space.
Vent Piping Guidelines
This gas furnace can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE: In non-Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
In Direct Vent installations, combustion air is taken from
outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing - Size pipe according to
Table 6 and Table 7A through Table 7C. Table 6 lists the
minimum vent pipe lengths permitted. Table 7A through
Table 7C list the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination.
Minimum Vent Pipe Lengths
Models
045, 070, 090, 110
*Any approved termination may be added to the minimum
length listed.
Page 16 of 52
CAUTION
CAUTION
Min. Vent Length*
15 ft or 5 ft plus 2 elbows or
10 ft plus 1 elbow
Table 6.
Use the following steps to correctly size vent pipe diameter.
Furnace capacity?
1
Which termination?
2
Which needs most
3
elbows?
How many?
4
Desired pipe size?
5
What is the altitude?
6
Use Table 7 to find
7
max pipe length.
In some applications which permit the use of several
different sizes of vent pipe, a combination vent pipe may
be used. Contact Allied Air Technical Service for assistance
in sizing vent pipe in these applications.
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
Issue 2327
045, 070,
090, 110
Standard or
Concentric?
See Table 4
Intake or
Exhaust?
1-1/2", 2",
2-1/2"
or 3"
Figure 22.
IMPORTANT
508391-01