Digital Outputs; Connector Pin Descriptions; Digital/Analogs - Generac Power Systems Power Zone 410 Technical Manual

Hide thumbs Also See for Power Zone 410:
Table of Contents

Advertisement

Input/Output and Connector Information

Digital Outputs

Default Signal Name
Engine Preheat (Diesel)
Fuel On Relay
Start On Relay
Low Fuel Level
High Fuel Level
Audible Alarm
Alarm On Relay
Spare Digital Output
Engine Control Unit Relay
Utility Transfer Relay
Generator Transfer Relay
Throttle Drive (PWM signal)
Throttle Enable
Automatic Voltage Regula-
tion (PWM1)
Automatic Voltage Regula-
tion (PWM2)

Connector Pin Descriptions

DIGITAL/ANALOGS

J5 24 Pin
Signal
1
Ruptured Tank
2
2-wire (ret)
3
2-wire Start(1)
4
2-wire Start(2)
5
Xfer Position1
6
Xfer Position2
7
Theft
8
Extern Charger
9
TriclopsYEL
10
TriclopsGRN
11
TriclopsRED
12
Triclops+5V
13
DualFuel1/Low Fuel Lvl
20
Range/Level
Connection
Relay Contacts
J10-9
(30 V, 5 A max)
Relay Contacts
J10-8
(30 V, 5 A max)
Relay Contacts
J10-7
(30 V, 5 A max)
Open Drain (+VBATT,
J5-13
1.7 A device limited)
Open Drain (+VBATT,
J5-14
1.7 A device limited)
Open Drain (+VBATT,
J9-6
1.7 A device limited)
Relay Contacts
J10-5
(30 V, 5 A max)
J10-6
Open Drain (+VBATT,
J10-13
1.7 A device limited)
Relay Contacts
J10-12
(30 V, 5 A max)
Relay Contacts
J10-16
(30 V, 5 A max)
Relay Contacts
J10-14
(30 V, 5 A max)
J10-15
Open Drain (+VBATT,
J2-6
1.7 A device limited)
Open Drain (+VBATT,
J2-7
1.7 A device limited)
Field+
J1-4
Field-
J1-2
Board Connection Description
5 V pullup
GND
5 V pullup (NO)
5 V pullup (NC)
5 V pullup (GEN)
5 V pullup (UTILITY)
5 V pullup (door closed pulled to GND)
5 V pullup (ext charger pulled to GND)
Open collector with 240 Ω resistor
Open collector with 240 Ω resistor
Open collector with 240 Ω resistor
+5 V for Triclops with 50 mA fuse
NG/LO_FUEL (open drain)
Wire #
567
0
183
183A
525
524
A1
BC1
819
817
818
820
502
Technical Manual Power Zone 410 Controller