Nortel SONET AccessNode Quick Reference Manual page 29

Abm bay cable connection
Hide thumbs Also See for SONET AccessNode:
Table of Contents

Advertisement

Figure 3-3
BIP power input and distribution schematic for bays equipped with ABM shelves
2 -48 V dc battery 6 AWG
30 A rating
2 -48 V dc return 6 AWG
1 -48 V dc battery 6 AWG
30 A rating
1 -48 V dc return 6 AWG
4 - 48 V dc batt. 6 AWG
10 A/15 A (Note)
4 -48 V dc return 6 AWG
30 A rating
F
L
T
R
3 -48 V dc batt. 6 AWG
10 A/15 A (Note)
3 -48 V dc return 6 AWG
30 A rating
F
L
T
R
ABM shelf
*
FLT
filter for talk battery
Note: BIP NT4K14AB.03 B and below = 10 A
BIP NT4K14AB.04 B and above = 15 A
AccessNode ABM Bay Cable Connection Quick Reference Guide Issue 1.0
ABM bay dc power requirements and connection 3-5
15 A
Common-equipment shelf *
15 A
Copper-distribution shelf 1
15 A
Copper-distribution shelf 3
15 A
Copper-distribution shelf 5
15 A
Copper-distribution shelf 7
Common-equipment shelf *
Copper-distribution shelf 1
Copper-distribution shelf 3
Copper-distribution shelf 5
Copper-distribution shelf 7
15 A
Common-equipment shelf *
15 A
Copper-distribution shelf 2
15 A
Copper-distribution shelf 4
15 A
Copper-distribution shelf 6
Common-equipment shelf *
Copper-distribution shelf 2
Copper-distribution shelf 4
Copper-distribution shelf 6
Cooling unit
Cooling unit
10 A
Copper-distribution shelf 1
10 A
Copper-distribution shelf 3
10 A
Copper-distribution shelf 5
10 A
Copper-distribution shelf 7
Copper-distribution shelf 1
Copper-distribution shelf 3
Copper-distribution shelf 5
Copper-distribution shelf 7
Cooling unit
Cooling unit
1 A
Test access card
10 A
Copper-distribution shelf 2
10 A
Copper-distribution shelf 4
10 A
Copper-distribution shelf 6
Test access card
Copper-distribution shelf 2
Copper-distribution shelf 4
Copper-distribution shelf 6
19 circuit breakers