CHAPTER 4 – OPERATION INSTRUCTIONS

4.1 START UP

1. Battery switch MCB2 must be on. ("ON" position).
2. Turn MCB1 (Input) switch into "ON" position.
3. Turn required output MCB's (Output) switches into "ON" position.
4. The equipment will start automatically when AC input is detected.
WARNING: Mains voltage will now be present at the output.

4.2 SHUT DOWN

1. Hold the front screen MAIN CONTROL ON/OFF BUTTON for 4 seconds, this will shut the
equipment off and display "off" on the front display.
Note: When the equipment is switched off, if mains are still available the batteries will
continue to charge.
2. Turn all Output MCB's (Output) switches into "OFF" position.
3. Turn MCB2 (Battery) switch into "OFF" position.
4. Turn MCB1 (Input) switch into "OFF" position.