CHAPTER 8 – TECHNICAL SPECIFICATION

8.1 GENERAL SPECIFICATIONS

Model
Nominal Output Rating
( CosØ : 0,8 ) kVA
Nominal Output Rating
( CosØ : 1 ) W
Audible Noise
Efficiency (Load Dependant)
Operating Temperature
( Ambient )
Altitude
Ventilation
Relative Humidity
Protection Degree
Standards
Transport

8.2 RECTIFIER SPECIFICATIONS

Model
Nominal Input Voltage
Max Input current (A) per
phase @100% resistive
load, No charge current.
Max Input current (A) per
phase @100% resistive
load, Full charge current.
Input MCB Fitted to Cabinet
Input Frequency Range
Input Power Factor
Input Voltage range
Input THDi
Input Protection
EL1005XA
0.5kVA
400 Watts
Upto 83% Inverter Mode / Upto 98% Changeover
Mode
<1000 meters (Above See level)
EN 62040-1, EN 62040-2, EN 61000-2-2, EN 61000-3-2, EN 61000-4-2
EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8
EN 50171
EL1005XA
2.3A
6A
Type C 10A
Fuses, Voltage & Frequency tolerance, Input power limit,
30
EL1012XA
1.25kVA
1000 Watts
0-40 °C
Forced
< 90%
IP 20
Packaged and On Pallet
EL1012XA
230 VAC 1 phase + N
5.2A
9A
Type C 16A
47 – 55Hz
>0.99
140 – 310 Vac
<5%
EL1030XA
3kVA
2400 Watts
Upto 86% Inverter Mode
/ Upto 98% Changeover
Mode
EL1030XA
12.6A
24.6A
Type C 25A