Main Processor Diagnostics; Communication Diagnostics - Trane Sintesis RTAF-SVX002D-EN Installation, Operation And Maintenance Manual

Air-cooled chillers, 500 tons
Table of Contents

Advertisement

Main Processor Diagnostics

Table 4.
Main processor diagnostics
Diagnostic Name
Economizer Discharge Pressure Sensor - xy
Economizer Disch Press Sensor- xy
Econ Disch Press Sensor xy
Economizer Discharge Temperature Sensor - xy
Economizer Disch Temp Sensor- xy
Econ Disch Temp Sensor xy

Communication Diagnostics

Notes:
The following communication loss diagnostics will not
occur unless that input or output is required to be
present by the particular configuration and installed
options for the chiller.
Communication diagnostics (with the exception of
"Excessive Loss of Comm" are named by the
Functional Name of the input or output that is no
longer being heard from by the Main Processor. Many
LLIDs, such as the Quad Relay LLID, have more than
Table 5.
Communications diagnostics
Affects
Diagnostic Name
Target Severity
Comm Loss: Economizer
Valve - xy
Comm Loss: Economizer
Cprsr
Valve - xy
Comm: Econ Valve xy
Comm Loss: Economizer
Discharge Pressure - xy
Comm Loss: Economizer
Cprsr
Disch Press - xy
Comm: Econ Disch Press
xy
Comm Loss: Economizer
Discharge Temp - xy
Comm Loss: Economizer
Cprsr
Disch Temp - xy
Comm: Econ Disch Temp
xy
RTAF-SVX002D-EN
Affects
Severity Persistence
Target
Cprsr
Normal
Cprsr
Normal
Active
Modes
[Inactive
Persistence
Modes]
Normal
Latch
All
Normal
Latch
All
Normal
Latch
All
Active Modes
[Inactive Modes]
Latch
All
Latch
All
one functional output associated with it. A comm loss
with such a multiple function board, will generate
multiple diagnostics. Refer to the Chiller's wiring
diagrams to relate the occurrence of multiple
communication diagnostics back to the physical LLID
boards that they have been assigned to (bound).
Communication loss diagnostics shall be timed based
on action (target status) and not annunciation on the
operator display.
Criteria
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Diagnostics
Reset
Criteria
Level
Bad sensor or LLID
Remote
Bad Sensor or LLID
Remote
Reset
Level
Remote
Remote
Remote
25