Parameter Assignment And Structure Of The Module/Channel Parameters - Siemens SIMATIC ET 200SP HA Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters
Error_
Error_
Cause
Code_
Code_
1
2
0xE1
0x01
Reserved bit set
0xE1
0x02
Invalid diagnostics enable bit set for operating mode
0xE1
0x04
Invalid value for hardware interrupt limit
0xE1
0x08
Invalid coding for interference frequency suppres‐
sion / integration time
0xE1
0x09
Invalid coding for smoothing
0xE1
0x10
Invalid measurement type
0xE1
0x11
Invalid measuring range
0xE1
0x13
Incompatible terminal block
0xE1
0x20
Incorrect call length or incorrect DS number
0xE1
0x21
Incorrect number of HART repetitions
Valid parameters
Only the values specified in the following are permitted. Values that are not listed are rejected
by the I/O module.
Each parameter data record is checked by the I/O module. If a parameter with errors is detected,
the complete data record is rejected and the parameters of the I/O module remain unchanged.
A.2
Parameter assignment and structure of the module/channel
parameters
Structure of data record 128
Data record 128 has a length of 68 bytes.
It contains module parameters and technology parameters of the 4 channels.
The channel and technology parameters are divided into parameters that influence the actual
analog value acquisition, diagnostics enables and basic parameters of the HART communication.
You can specify and change other parameters or HART-specific settings with data records 131 to
134. See section HART-specific settings (Page 82).
58
Remedy
Check and correct the parameters
AI 4xI 2-/4-wire HART ISOL HA