Toshiba MMD-UP0721HFP Series Service Manual page 46

Table of Contents

Advertisement

[The example of Card Input 5 setting]
Code No. (DN) setting
Case.
[16A]
[16b]
[16C]
[16d]
[16F]
data
data
data
data
data
(1) 0000 0000 0027 0020 0000 0000 0000 0024 0024
(2)* 0000 0001 0027 0020 0003 0001 0001 0024 0024
(3)* 0000 0002 0027 0020 0003 0001 0001 0024 0024
(4) 0001 0000 0027 0020 0003 0001 0001 0024 0024
* The history operation mode is only recorded when the card is inserted even if the operation mode is changed when the
card is taken out, there is no related to the history operation mode.
Power peak-cut from indoor unit
When the relay is turned on, a forced thermostat OFF operation starts.
• For indoor P.C. boards other than MCC-1643, the "EXCT" is input with connector CN73 on the P.C. board.
MCC-1643 requires Application control kit (TCB-PCUC2E) for input of a forced thermostat OFF "EXCT".
Please refer to the manual of Application control kit for a detailed setting.
• Wiring example
CN73
1
1
2
2
EXCT
(2P plug: RED)
Indoor control P.C. board
[170]
[171]
[172]
[173]
Close (Status that card is inserted) Open (Status that card is taken n out)
data
data
data
data
• The operation mode continues running
at the same as the current mode.
• The setting temperature of cooling/dry
and heating mode is changed to 24ºC
and 24ºC respectively due to change in
code No. 172, 173.
• The operation mode is running at the
same mode as the last time when the
card was inserted due to change in code
no. 16b.
* The operation mode will be off if the
mode at the last time was in off operation.
Also, the fan speed will the same as
the last time when the card is inserted.
• The setting temperature of cooling/dry
and heating mode is changed to 24ºC
and 24ºC respectively due to change in
code No. 172, 173.
• The operation mode is running at the
same mode as the last time when the
card was inserted. Also, the operation
mode will be on even the mode was in
off operation at the last time due to
change in code no. 16B.
* The fan speed will the same as the last
time when the card is inserted.
• The setting temperature of cooling/dry
and heating mode is changed to 24ºC
and 24ºC respectively due to change in
code No. 172, 173.
• The operation mode continues running
at the same as the current mode.
• The setting temperature of cooling/dry
and heating mode is changed to 24ºC
and 24ºC respectively due to change in
code No. 172, 173.
Relay (procured locally)
Relay coil signal
External contact terminal
Note) Determine the cable length between the indoor or
outdoor control P.C. board and the relay within 2 m.
- 46 -
• The operation mode continues running
at the same as the current mode.
• The setting temperature of cooling/dry
and heating mode is changed to 27ºC
and 20ºC respectively due to change in
code No. 16C, 16d.
• The operation mode continues running
at the same as the current mode.
• The setting temperature of cooling/dry
and heating mode is changed to 27ºC
and 20ºC respectively due to change in
code no. 172, 173.
• The fan speed for all operation modes is
changed due to change in code no.16F.
• The wind direction of Cooling/dry/fan
and heating mode are changed due to
change in code No. 170, 171 respectively.
Same operation as case (2)
• Due to change in code no. 16A, the
operation mode will be as below.
• When the operation is ON, the
operation mode will continue running at
the same as the current mode.
• When the operation is OFF, the air
conditioner will turn on automatically.
• The setting temperature of cooling/dry
and heating mode is changed to 27ºC
and 20ºC respectively due to change in
code No. 172, 173.
• The fan speed for all operation modes is
changed due to change in code no.16F.
• The wind direction of Cooling/dry/fan
and heating mode are changed due to
change in code No. 170, 171 respectively.

Advertisement

Table of Contents
loading

Table of Contents