Type
CODE No. (DN) "10"
Setting data
0000
1-way Ceiling Cassette
4-way Ceiling Cassette
0001
※1
0002
2-way Ceiling Cassette
0003
1-way Ceiling Cassette (compact)
0004
Concealed Built-In
Concealed Compact Duct
0005
0006
Concealed Duct
0007
Under Ceiling
0008
High Wall
0009
Under Ceiling for Kitchen
0010
Floor Standing Console
0011
Floor Standing Consealed
0012
Floor Standing (8/10hp)
0013
Floor Standing (up to 6hp)
0014
Compact 4-way Ceiling Cassette
0016
Air conditioner for outside air processing
~
-
1: Default value stored in EEPROM mounted on service board
■ How to set fan operation during defrosting
Since the air conditioner for outside air processing gives priority to the introduction of outside air, the fan operation can be set even
during defrosting.
Set the CODE No. (DN) "72"=0000 (fan ON when defrosting).
Set the CODE No. (DN) "9B"=0002 (no hot start control).
■ How to All Fresh Air Intake Unit connect setting
(Case of SMMS-e series)
When only Fresh Air Intake Units connected to Outdoor unit, set the all Fresh Air Intake Unit connection setting at Fresh Air Intake Units.
Set DN data is below :-
Type
MMU-
MMU-
MMU-
MMU-
MMU-
MMD-
MMD-
MMD-
MMC-
MMK-
MMK-
MMC-
MML-
MML-
MMF-
MMF-
MMU-
MMD-
DN
C8
AE
AF
NOTE : Firstly, set up CODE No. (DN) "C8", then change other two CODEs.
Model
P
SH
 ※ ※
 ※ 
P
H
 ※ ※
 ※ 
P
HD
 ※
 ※ ※
P
WH
 ※
 ※ ※
P
YH
 ※
 ※ ※
P
BH
 ※
 ※ ※
P
NH(L)
 ※ ※
 ※
P
H
 ※ ※
 ※
P
H
 ※ ※
 ※
P
H
 ※
 ※ ※
P
H-1
 ※
 ※ ※
P
PH
 ※ ※
 ※ 
P
H
 ※ ※
 ※ 
P
BH
 ※ 
 ※ ※
P
H
 ※
 ※ ※
P
H
 ※ 
 ※ ※
P
MH
 ※ 
 ※ ※
P
HF
 ※
 ※ ※
SET DATA
0000
0016
0010
- 41 -
Indoor unit capacity
CODE No. (DN) " 11 "
Setup data
Ability rank
0000
Invalid
007 type
0001
008 type
0002
009 type
0003
010 type
0004
012 type
0005
014 type
0006
015 type
0007
017 type
0008
018 type
0009
020 type
0010
024 type
0011
027 type
0012
030 type
0013
036 type
0015
048 type
0017
056 type
0018
072 type
0021
096 type
0023
112 type
0024
128 type
0025
1: Default value stored in EEPROM