Fault Detection

When the Drive detects a fault, the fault information is displayed on the digital operator, the fault contact closes, and the motor
coasts to stop. (However, a fault with selectable stopping method will operate according to the stopping method selected.)
• If a fault occurs, take appropriate action according to the table by investigating the cause.
• To restart, reset the fault with any of the following procedures:
• Turn ON the fault reset signal.
• Set "14: Fault Reset" to a multi-function digital input (H1-01 to H1-05).
• Press the RESET key of the digital operator.
• Shut off the Drive input power once, and then turn on again.
The Run Command (Start Command) needs to be removed prior to resetting a fault. Resetting a fault by
removing and reapplying power to the Drive while the Run Command is applied, may cause the Drive to start
WARNING
unexpectedly. Therefore, make sure all personnel are clear from the Drive, motor, and machine prior to reset-
ting the Drive.
Digital
Operator Display
Option Communication Error
BUS
After initial communication was
Option Com Err
established, the connection was lost.
CE
Modbus Communication Error
Memobus Com Err
Control data was not received correctly for
two seconds
Operator Communication Fault 1
Transmission between the Drive and the
digital operator cannot be established
CPF00
within 5 seconds after supplying power
COM-ERR(OP&INV)
External RAM of CPU is defective
Operator Communication Fault 2
CPF01
After communication started with the
COM-ERR(OP&INV)
digital operator, a communication fault
occurred for 2 seconds or more
CPF02
Baseblock Circuit Fault
BB Circuit Err
Baseblock circuit fault at power-up
CPF03
EEPROM Fault
EEPROM Error
EEPROM fault, check sum not valid
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 6.1 Fault Displays and Processing
Description
Connection is broken, master
has stopped communicating
Connection is broken, master
has stopped communicating
Digital operator cable not
securely connected, digital
operator defective, control
board defective
Control circuit damage
Digital operator cable not
securely connected, digital
operator defective, control
board defective
Gate array hardware failure
during power-up
Diagnostic & Troubleshooting 6 - 2
Cause
Noise or spike on the control
circuit input terminals
Corrective Action
Check all connections, verify all
user-side software configurations.
Check all connections, verify all
user-side software configurations.
Remove the digital operator once
and then reinstall it
Cycle power off and on to the
Drive
Replace the Drive
Remove the digital operator once
and then reinstall it
Cycle power off and on to the
Drive
Replace the Drive
Perform a factory initialization
Cycle power off and on to the
Drive
Replace the control board
Perform a factory initialization
Cycle power off and on to the
Drive
Replace the control board