Lennox A98USMV Installation Instructions Manual page 64

Warm air gas furnace upflow/horizontal left/right air discharge direct vent
Table of Contents

Advertisement

Code
Diagnostic Codes / Status of Equipment
E407
LSOM - Compressor open run circuit.
E408
LSOM - Compressor contactor is welded.
E409
LSOM - Compressor low voltage.
Page 64 of 74
Action Required to Clear and Recover
Required amount of current is not passing through
Run current transformer. Clears the error after current
is sensed in RUN sensor, or 1 normal compressor run
cycle, or after power reset.
Compressor runs continuously. Clears the error after 1
normal compressor run cycle or after power reset.
Secondary voltage is below 18VAC. After 10 minutes,
operation is discontinued. Clears the code after voltage
is higher than 20VAC for 2 seconds or after power
reset.
Issue 2346
508364-01