6.4.2

Grounding connection type

Type of enclosure grounding
 
 
Connection of an individual conductor under the
external grounding bracket.
 
 
 
 
Connection is made using a DIN cable lug under
the external grounding bracket. DIN 46 234
 
 
Internal ground terminal
Comply with the following instructions when connecting up:
• Ensure that the connecting surface is bare and is protected against corrosion using a suitable
substance, e.g. acid-free Vaseline.
• Arrange the spring lock washer under the screw head.
• Locate the cable lug under the clamping bracket.
• Use the terminals designated for the grounding conductor in the terminal box.
• Observe the tightening torque for the locking screw.
External ground terminal
Comply with the following instructions when connecting up:
• Ensure that the connecting surface is bare and is protected against corrosion using a suitable
substance, e.g. acid-free Vaseline.
• Locate the cable lug between the contact bracket and the grounding bracket; do not remove
the contact bracket pressed into the enclosure.
• Arrange the flat washer and spring washer under the bolt head.
• Use the marked connection location for the grounding conductor on the stator housing.
• Observe the tightening torque for the locking screw.
1LE1, 1FP1/3, 1PC1/3 shaft height 63 ... 315
Operating Instructions, 11/2023, A5E38483075A
Electrical connection
6.4 Connecting the grounding conductor
Conductor cross-sec‐
tion
mm²
 
... 10
... 25
71