Daikin FCA71AV16 Installation Manual page 28

Table of Contents

Advertisement

12-1 CAUTIONS FOR SERVICING
With the power on. Troubles can be monitored on the remote controller.
• If the air conditioner does not operate normally after installing the air conditioner.
a malfunction shown in the table below may happened.
Remote controller display
*After turning on the power, the maximum is 90 seconds, although it will only display "Checking the
connection. Please stand by". This is not a problem, and it will be set for 90 seconds.
** For fault diagnosis for BRC1 H model remote controller should be performed while referring to the indoor
operation manual.
I
No display
• Power supply trouble or Open phase connection
• Wrong wiring between indoor and outdoor unit
• Indoor PC board faulty
• Wrong remote controller conection wiring
• Remote controller faulty
• Fuse faulty
27
Malfunction